How to Check a 240V Outlet

Quck answer

To test a 240V outlet, follow these steps:

1. Turn off the power to the outlet at the circuit breaker.

2. Use a voltage tester or multimeter to check for voltage at the outlet. Place one probe in each of the hot slots of the outlet. If there is voltage, the tester will indicate a reading of around 240V.

3. If there is no voltage, check the circuit breaker to make sure it is switched on. If it is on and there is still no voltage, there may be a wiring issue or a problem with the outlet itself.

4. If there is voltage, turn off the power again and inspect the outlet for any signs of damage or loose connections. Repair or replace the outlet as needed.

5. Finally, turn the power back on and retest the outlet to ensure it is functioning correctly.


Most of the sockets in a typical home function at 120 volts, and these are the ones where you plug in lamps and small appliances. Alongside these, most houses have at least one 240-volt socket to power larger, energy-intensive appliances like dryers, air conditioners, and stoves. If you’re experiencing issues with an appliance plugged into one of these sockets, the problem could be with the power supply to the socket, and you can test the socket for voltage just like you would test a 120-volt socket.

This test is best performed using a multimeter. It is important to note that the higher voltage presents a higher risk of electric shock, so it is crucial to follow safety protocols. One of the safest precautions you can take is to wear rubber gloves during the testing procedure, and it is also advisable to wear rubber-soled shoes to prevent electric current from passing through your body.

What to Anticipate From the Test

In today’s world, the National Electrical Code (NEC) mandates that all 240-volt sockets must be grounded, and if the socket you are testing complies with the code, it will have four slots. These slots may be angled or a combination of horizontal and vertical, but regardless of their orientation, the two outermost slots are connected to the hot wires, while the slots between them are connected to the ground and neutral wires. The neutral slot is usually on top, but for the purpose of the test, it doesn’t matter which is which.

Sockets installed before the NEC changed the regulations might not always be grounded and may only have three slots, but the wiring configuration is the same. The two outermost slots are hot, and the slot in the middle is neutral. As long as you remember these configurations, the rest of the test is straightforward.

Directly Testing the Socket

You can directly test a 240-volt socket by inserting the multimeter probes into the slots. The advantage of this method is that it does not require turning off the power. The procedure is more or less the same for 3- and 4-slot sockets.

Set the meter to read voltage in a range that can measure at least 240 volts. Put on rubber gloves, hold the probes, insert one into each of the outermost slots, and check the reading. If the socket is live, you should get a reading of 240 volts ±10 percent. A reading of 215 volts is acceptable, as is a reading of 260 volts.

Now remove one probe and insert it into the ground or neutral slot, and you should get a reading of 120 volts ±10 percent. Now remove the probe from the hot terminal and insert it into the other hot terminal, and you should get the same reading.

Tip

Be extremely cautious to prevent the probes from making contact with each other during the test. If they touch, they will create a short circuit, which can potentially shock you, and the resulting spark can damage the socket or the meter.

Testing for a Faulty Socket

If you suspect a faulty outlet, you may want to check the wiring to see if it is delivering the correct voltage. To do this, first turn off the circuit breaker, unscrew the outlet, and pull it out to gain access to the wiring. Then turn the breaker back on to conduct the test.

Place the probes on the two brass terminals that the red and black wires are attached to. The meter should display a reading of 240 volts. Next, place one probe on either of the hot terminals and the other probe on the ground or neutral terminal to confirm a reading of 120 volts. Repeat this test with the other hot terminal and ground or neutral. If you obtain the expected readings and the receptacle is still not functioning, it is faulty and should be replaced.

Leave a Comment